Значения термо-ЭДС для термопары типа ТМК(M) шаг 20 °C

термо-ЭДС, мВ
Температура, °C +0 +2 +4 +6 +8 +10 +12 +14 +16 +18
-200 -6.154 -6.12 -6.084 -6.049 -6.012 -5.975 -5.938 -5.9 -5.861 -5.821
-180 -5.781 -5.741 -5.7 -5.658 -5.616 -5.573 -5.529 -5.485 -5.44 -5.395
-160 -5.349 -5.303 -5.256 -5.208 -5.16 -5.111 -5.062 -5.012 -4.962 -4.911
-140 -4.859 -4.807 -4.755 -4.701 -4.648 -4.593 -4.539 -4.483 -4.427 -4.371
-120 -4.314 -4.256 -4.198 -4.14 -4.081 -4.021 -3.961 -3.9 -3.839 -3.778
-100 -3.715 -3.653 -3.59 -3.526 -3.462 -3.397 -3.332 -3.266 -3.2 -3.133
-80 -3.066 -2.998 -2.93 -2.861 -2.792 -2.723 -2.652 -2.582 -2.511 -2.439
-60 -2.367 -2.295 -2.222 -2.149 -2.075 -2 -1.926 -1.85 -1.775 -1.699
-40 -1.622 -1.545 -1.468 -1.39 -1.311 -1.233 -1.153 -1.074 -0.994 -0.913
-20 -0.832 -0.751 -0.669 -0.587 -0.504 -0.421 -0.338 -0.254 -0.17 -0.085
0 0 0.085 0.171 0.258 0.344 0.431 0.519 0.607 0.695 0.784
20 0.873 0.962 1.052 1.142 1.232 1.323 1.415 1.506 1.598 1.691
40 1.783 1.876 1.97 2.064 2.158 2.252 2.347 2.442 2.538 2.634
60 2.73 2.826 2.923 3.021 3.118 3.216 3.314 3.413 3.512 3.611
80 3.71 3.81 3.91 4.011 4.111 4.213 4.314 4.416 4.518 4.62
100 4.722

Комментарии

Странник

в списке термопар нет нужной мне - Tp01A и преобразование из милливольт от термопары в температуру вообще не работает.

Администратор

Здравствуйте. Tp01A не является стандартным типом термопары. Могу лишь сказать что в быту обычно встречаются термопары типа ТХА(K), что скорее всего подойдёт и в вашем случае. Описанной вами проблемы не вижу, была проблема с корректностью подсчёта как раз таки для типа K, но я её нашёл и устранил. Если есть ещё какие-то проблемы буду благодарен за подробное объяснение.